Тип | Р, МВт | cos φ | Q, Мвар | кВ | КПД, % | % | r, % | К % | X., % | % | % | окз | тм5 | Част, вращения 1 мин | T ,с |
Серия ВГС | |||||||||||||||
ВГС-1525/135-120 | 57,2 | 0,85 | 35,8 | 10,5 | 97,2 | 29,0 | 34,0 | 66 | 17,5 | — | 11,5 | 1,78 | 73 000 | 50 | 3,81 |
ВГС-1260/147-68 | 82,5 | 0,85 | 52,3 | 13,8 | 97,5 | 21,0 | 28,0 | 76 | 14,0 | — | — | 1,47 | 37 000 | 88,2 | 5,0 |
ВГС- 1260/200-60 | 150 | 0,85 | 93,0 | 15,75 | 97,6 | 25,0 | 35,0 | 102 | 16,0 | — | — | 1,10 | 58 000 | 100 | 8,2 |
ВГС-930/233-30 | 294 | 0,85 | 182,0 | 15,75 | 98,25 | 19,0 | 33,0 | 147 | 12,4 | 20 | — | 0,75 | — | 200 | — |
ВГСВФ-940/235-30 | 353 | 0,85 | 219,0 | 15,75 | 98,2 | 24 | 38 | 131 | — | 25 | - | 0,8 | - | 200 | - |
Серия СВ | |||||||||||||||
СВ-375/195-12 | 52,4 | 0,8 | 39,2 | 10,5 | 97,4 | 16,0 | 28,0 | 130 | — | — | — | 0,86 | 4000 | — | — |
СВ-430/210-14 | 55 | 0,8 | 41,3 | 10,5 | 97,559 | 18,0 | 28,0 | 114 | — | 19,0 | — | 1,01 | 825 | 428 | 5,45 |
СВ-1250/1 70-96 | 55 | 0,8 | 41,3 | 13,8 | 7,3 | 33,0 | 33,0 | 77,0 | - | - | — | — | — | — | — |
СВ-660/165-32 | 57 | 0,8 | 42,7 | 10,5 | 97,5 | 19,0 | 29,0 | 104 | — | 20,1 | — | 1,12 | 4500 | 188 | 5,80 |
СВ-1340/140-96 | 57,2 | 0,8 | 43,0 | 13,8 | 96,7 | 21,0 | 29,0 | 63,0 | 12,1 | 21,2 | 8,0 | 1,78 | 51 700 | 62 | 4,33 |
СВН(СВК,СВКС)-1340/150-96 | 57,2 | 0,8 | 43,0 | 13,8 | 96,88 | 21,0 | 29,0 | 63,0 | 12,1 | — | — | 1,63 | 73 000 | 50 | 3,81 |
СВ-780/137-32 | 63 | 0,85 | 39,4 | 10,5 | 97,95 | 17,0 | 26,0 | 88,0 | 10,4 | - | — | — | — | — | |
СВ-640/170-24 | 67 | 0,85 | 41,5 | 13,8 | 97,62 | 20,0 | 27,0 | 107 | - | — | — | 1,03 | 4000 | 250 | — |
СВ-1130/140-48 | 117,7 | 0,85 | 88,5 | 13,8 | 98 | 21,0 | 26,0 | 91,0 | — | 22 | 10 | - | 7250 | 125 | — |
СВ-850/ 190-48 | 75 | 0,85 | 46,9 | 13,8 | 97,55 | 23,0 | 28,0 | 91,0 | — | — | — | — | — | — | — |
СВ-850/1 90-48 | 72,5 | 0,85 | 45,0 | 16,5 | 97,5 | 23,0 | 32,0 | 87,0 | - | 23,1 | 11,0 | 1,30 | 14 080 | 125 | 6,75 |
СВБ-750/211-40 | 75 | 0,85 | 46,9 | 13,8 | 97,85 | 23,0 | 28,0 | 91,0 | 15,6 | — | — | — | — | ||
СВВ-780/ 190-32 | 77 | 0,85 | 48,2 | 13,8 | 97,66 | 15,0 | 24,0 | 85,0 | 9,6 | — | - | — | 9500 | 188 | — |
СВ-850/190-40 | 90 | 0,9 | 43,2 | 16,5 | 98,0 | 19,0 | 27,0 | 87,0 | - | 19,8 | 9,1 | 1,52 | 16000 | 150 | 6,48 |
СВ-850/190-40 | 100 | 0,9 | 48,0 | 13,8 | 98,2 | 26,0 | 37,0 | 97,0 | 17,2 | 26,2 | 12,0 | 1,10 | 16 000 | 180 | 7,6 |
CD-1500/170-96 | 100 | 0,85 | 62,5 | 13,8 | 97,5 | 21,0 | 29,0 | 65,0 | — | 21,7 | 8,9 | 1,75 | 88 000 | - | 5,02 |
СВ-1225/130-56 | 108,5 | 0,85 | 68,0 | 13,8 | 98,29 | 24,0 | 34,0 | 93 0 | 16,0 | — | — | — | |||
В 1500/200-88 | 127,8 | 0,9 | 56 | 13,8 | 97,6 | 15,0 | 20,0 | 52,0 | — | 15 | - | - | 25 000 | 68,2 | — |
СВ-855/235-32 | 150 | 0,9 | 72,0 | 13,8 | 98,07 | 17,0 | 28,0 | 100 | — | 16,5 | 5,1 | 1,12 | 18 000 | 187,5 | — |
СВ-1500/175-84 | 171 | 0,9 | 82,0 | 15,75 | 98,3 | 26,0 | 37,0 | 110 | - | 28,0 | 10,0 | 0,97 | 82 000 | 71 5 | 6,5 |
СВ-1190/250-48 | 225 | 0,85 | 140 | 15,75 | 97,44 | 24,0 | 35,0 | 107 | 16,4 | 24,4 | 13,6 | 1,04 | 57 200 | 125 | 9,5 |
СВ-712/227-24 | 260 | 0,85 | 162 | 15,75 | 98,15 | 28,8 | 42,0 | 165 | 17,8 | 27,0 | 10,0 | 0,64 | 8000 | 250 | 8,8 |
СВ-1100/250-36 | 300 | 0,85 | 187 | 15,75 | 98,4 | 20 | 33,0 | 130 | — | 20,0 | 40,0 | — | 43 000 | 165 7 | 5,1 |
Серия СВФ | |||||||||||||||
СВФ-1500/130-88 | 128 | 0,8 | 96,0 | 13,8 | 96,3 | 40,0 | 57,0 | 175 | 40,9 | 12,5 | 0,62 | 110 000 | 68,2 | 3,44 | |
СВФ-990/230-36 | 300 | 0,85 | 183 | 15,75 | 98,2 | 24,0 | 37,0 | 134 | 13,6 | — | — | — | — | — | — |
СВФ-1690/175-64 | 500 | 0,85 | 310 | 15,75 | 98,25 | 30,0 | 42,0 | 158 | 30,7 | 8,4 | 0,67 | 187 000 | 93,8 | 5,10 | |
СВФ-1285/275-42 | 640 | 0,9 | 315 | 15,75 | 98,3 | 29,5 | 43,0 | 158 | — | 30,5 | 15,0 | 0,66 | 102 000 | 142,8 | 5,10 |
Капсульные гидрогенераторы | |||||||||||||||
СГКВ-480/115-64 СГВК-720/140-80 | 20 45 | 1,0 0,98 | 0 5,0 | 3,15 6,3 | 96,3 97,0 | 45,0 39,0 | 57,0 76,0 | 194 106 | : | : | — | 0,58 0,68 | 3000 | 93,8 75 | |
Обратимые гидрогенераторы | |||||||||||||||
СВО-733/130-36 | 33,4 40 | 0,73/0,91 0,9 | 35/19,0 19,2 | 10,5 10,0 | 96,9 97,4 | 22,0 24,0 | 33,0 37,0 | 103 114 | - | - | 22,0 24,0 | 5,75 5,75 | |||
— | — | — | — | — | |||||||||||
В ГДС-1005/245-40 | 200 | 0,85 | 124 | 15,75 | 98,4 | 32,0 | 45,0 | 142 | - | 33 | 12,0 | 0,8 | 32 000 | 150 | 12,8 |